(4) To fully optimize the PV DC output set-up, use the following confi-
guration guidelines:
(a) For PV DC output less than 8.5 A, use a single pair of PV-Inverter
DC terminals.
(b) For PV DC output between 8.5 A and 17 A, use two sets of inver-
ter DC terminals.
(c) For PV DC output between 17 A and 25.5 A, use 3 sets of inver-
ter DC terminals.
5.5 connEcting to thE connEction unit
The AC connection unit is an interface between your PV-Inverter and
the Public grid. It may consist of an electrical breaker, fuse and ter-
minals for connection to both PV-Inverter and the Public grid. This
Connection unit must be designed by qualified technician to comply
with local safety standards.
AC-Out Cable
( 2.0 mm²)
AC-Output Port
AC connection unit
(consisting of breaker,
fuse, terminals etc.)