4.8.3 Wiring box conduit openings
Figure 26: Wiring box conduit opening locations
Conduit openings are provided for 1 inch and ½ inch conduit ttings. If the conduit tting used
is between 1 inch and ½ inch (2.54 cm and 1.27 cm), an appropriate conduit reducer should be
used.
Do not enlarge the wiring compartment conduit openings as the
wiring box enclosure will be damaged which will void the inverter
warranty.
CAUTION!
PRUDENCE!
1 in.
1 in. 1 in.
1 in.
1/2 in.
Figure 27: Wiring box conduit plug removal (illustration showing
the removal of a conduit plug)
The conduit plugs are removed by pla-
cing a at head screwdriver in the slot
on the conduit plug face and turning it
while gripping the nut on the inside of
the enclosure. Unscrew the nut from
the conduit plug and slip the conduit
plug out of the conduit opening.