PV Powered LLC 32-29-28-20-306 PVP3200, PVP2900, PVP2800-XV and PVP2000 Installation and Operation Manu
PV Powered LLC 9 32-29-28-20-306 2.3.b Connecting the StarInverter to the Electrical Grid Inside the StarInverter are two circuit boards: ♦
PV Powered LLC 10 32-29-28-20-306 4. Connect the LINE 2/NEUTRAL wire to the terminal marked ‘line 2/neutral’ inside the StarInverter. 5.
PV Powered LLC 11 32-29-28-20-306 To wire the DC inputs from the PV panels to the StarInverter (refer to Figure 10): Note: Each DC input
PV Powered LLC 12 32-29-28-20-306 3.0 OPERATION 3.1 Start Up Procedures for the StarInverter WARNING: Before turning on the StarInverter
PV Powered LLC 13 32-29-28-20-306 If at any moment the operating environment moves outside the safe operating limits, governed by UL 1741, IEE
PV Powered LLC 14 32-29-28-20-306 4.0 TROUBLESHOOTING If the StarInverter’s “STAND BY” LED remains red for a prolonged period (longer than t
PV Powered LLC 15 32-29-28-20-306 For example: EX 1: Fault Code 1000 0000 0480 The first code indicates this is a voltage fault of some kin
PV Powered LLC 16 32-29-28-20-306 5.0 SPECIFICATIONS Specifications PVP3200-240 PVP2900-208 PVP2800-XV PVP2000-120 Maximum System Volta
PV Powered LLC 17 32-29-28-20-306 6.0 LIMITED WARRANTY PV Powered, LLC provides a limited warranty that covers defects of your StarInverter
PV Powered LLC 18 32-29-28-20-306 ALL CAUSES OF ACTION, WHETHER IN CONTRACT, TORT OR OTHERWISE, WILL NOT EXCEED THE AMOUNT PAID TO PV POWERED
PV Powered LLC 1 32-29-28-20-306 StarInverter PVP3200, PVP2900, PVP2800-XV and PVP2000 Table of Contents IMPORTANT SAFETY INSTRUCTIONS 2 1.0
PV Powered LLC 19 32-29-28-20-306 On the packaging please include the following: 1. The Return Authorization Number supplied by PV Powered c
PV Powered LLC 20 32-29-28-20-306 Notes:
PV Powered LLC 21 32-29-28-20-306
PV Powered Delivering Tomorrow’s Solar Technology . . . Today PV Powered, LLC 150 SW Scalehouse Loop, #101 Bend, OR 97702 Phone 541-312-3832 •
PV Powered LLC 2 32-29-28-20-306 IMPORTANT SAFETY INSTRUCTIONS This product has been engineered and manufactured to ensure your personal saf
PV Powered LLC 3 32-29-28-20-306 SAVE THESE INSTRUCTIONS 1.0 INTRODUCTION The PV Powered StarInverter is a utility interactive inverter for
PV Powered LLC 4 32-29-28-20-306 In choosing a location for the StarInverter, consideration should be given to the following criteria: ♦ The
PV Powered LLC 5 32-29-28-20-306 CAUTION: To reduce the risk of fire, connect the PVP3200, PVP2900 and PVP2800-XV to a circuit with 20 amps ma
PV Powered LLC 6 32-29-28-20-306 Figure 3: Inside screws, located below the power board Figure 4: Mounted StarInverter with Mounting
PV Powered LLC 7 32-29-28-20-306 2.3 Electrical Connection Do not proceed with the electrical connection of the StarInverter until it has b
PV Powered LLC 8 32-29-28-20-306 2.3.a Grounding ♦ A single point ground connection is located in the lower right hand side of the StarInver