PV Powered PVP4800 Spécifications Page 10

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 23
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 9
PV Powered LLC 9 32-29-28-20-306
2.3.b Connecting the StarInverter to the Electrical Grid
Inside the StarInverter are two circuit boards:
The Control Board
The Power Distribution Board with a D-sub socket or an optional terminal block
for communications to a personal computer and:
The AC connection terminal
The DC connection terminal
The Internal AC grid fuse(s)
The Internal Ground Fault Interrupt fuse
WARNING: For continued protection against risk of fire, replace only with
same type and ratings of fuse. The PVP2500, PVP3500 and PVP4800 all use only
Littelfuse 326020 30 AMP 250V AC.
PV Powered provides overcurrent protection on the Power Distribution Board with two 30
AMP fuses in the PVP2500, PVP3500 and PVP4800 (See warning above). Additional over
current protection for the inverter’s AC output is provided by circuit breakers at the
breaker panel.
WARNING: Replace GFI fuse with only same type and rating of fuse. The
PVP2500, PVP3500 and PVP4800 uses only Littelfuse KLKD001 1A/600V.
The StarInverter is connected to the electrical grid using 3 wires - the LINE 1, LINE
2/NEUTRAL and GROUND.
Please Note: To avoid an increase in AC voltage to unacceptable values while the
StarInverter is connected, the grid impedance value at the connection point should
be as low as possible. By keeping the grid impedance value low, higher system
efficiency will be achieved.
The total impedance of the grid plus the interconnecting AC wires should be less
than 1.25 Ohm.
WARNING: Make sure the main 240 V breaker at the circuit breaker panel is
switched OFF before you connect the AC terminal block.
To wire the StarInverter to the main utility grid, follow the steps outlined below (refer to
Figure 8):
1. Run the conduit from the main breaker panel to the bottom of the StarInverter
and insert the fitting in the center opening of the StarInverter, fastening with a
locking nut.
2. Feed the LINE 1, LINE 2/NEUTRAL and GROUND wires through the conduit and
into the center opening of the StarInverter.
3. Connect the GROUND wire to the terminal marked ‘earth ground’ inside the
StarInverter.
Vue de la page 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 22 23

Commentaires sur ces manuels

Pas de commentaire